Differential pressure in cleanrooms: pressure cascades and sensor selection

Differential pressure in a cleanroom is the pressure difference between two defined areas. It helps to assess the intended pressure relationships between the cleanroom, airlock, and surroundings. For reliable measurement, the reference area, pressure tapping points, measurement range, and permissible measurement deviation must be compatible. This article explains the measurement principle and shows how specialist planners and system manufacturers structure the sensor selection from the pressure cascade to the evaluation.

Back to blog

Why is differential pressure measured in the cleanroom?

In product protection, airflow should be directed from a cleaner area into a less clean area. A correspondingly higher room pressure supports this principle. In a containment application, however, a different pressure concept may be required to retain substances within the designated area. Positive and negative pressure therefore serve different protection objectives.

The measured value is always a difference: Δp = p+ − p−. The sign is determined by the assignment of the pressure connections. A positive value alone does not explain whether the system is operating correctly. To determine this, the monitored zone, reference room, operating state, and target range must be known.

Room differential pressure must also be distinguished from filter differential pressure. Room pressure measurement compares two areas. Filter measurement records the pressure drop across a filter. The respective working areas can be significantly apart. For device selection, you will find different designs and measurement tasks in the pressure range.

A pressure value does not replace an inspection of the actual airflow. Airflow direction, door status, and system operation must be taken into account when evaluating.

  • Reference

    Which room is being compared with which other area? Clearly document the print samples and connection assignment.

  • Workspace

    Consider normal operation, door movements, standstill, and possible polarity reversals when defining the measuring range.

  • Measurement deviation

    Assess accuracy at the relevant operating point. Consider resolution, zero point, and drift separately from the full scale.

  • Evaluation

    Define the signal path, display, recording, and alarm response. Commission and test the complete measurement chain.

Correctly classifying the pressure cascade in the cleanroom

A pressure cascade describes coordinated pressure levels in adjacent zones. A simplified example sets the ambient environment at 0 Pa, the airlock at +15 Pa, and the critical area at +30 Pa, each relative to the same reference point. This results in a pressure differential of 15 Pa between adjacent zones. The graphic is a calculation example and not a general design specification.

For the manufacture of sterile medicinal products, EU GMP Annex 1, Section 4.14, specifies at least 10 Pa as a guideline between adjacent rooms of different grades. This specification applies in this technical context; it is not a universal setpoint for all cleanroom applications. Containment tasks may require different pressure concepts.

Setpoints, tolerances, and alarm limits must align with the protection concept. Also define how door openings and other operating conditions are assessed. The authoritative primary source is EU GMP Annex 1, Sections 4.14 to 4.16.

Clearly assign pressure tapping points to the measurement chain

A measurement channel is connected to the two pressure points to be compared. In the illustrated principle, the higher pressure is applied to p+ and the lower pressure to p−. The installation instructions for the specific device provide information on the available connections and their designations.

Position the pressure tapping points so that they accurately represent the intended room pressure differential. Local influences caused by airflow patterns can affect the measurement results. Accessibility, cleaning, tubing routes and leak-tight connections should therefore be considered during the planning stage. Avoid kinks and check the tubing installation according to the manufacturer's specifications.

During commissioning, verify the correct assignment of the connections and the pressure differential sign, as well as the zero point, selected measuring range and signal transmission. For 0–10 V or 4–20 mA signals, the scaling in the receiving system must match. For bus-enabled devices, check the registers, units and communication settings.

The illustration shows the measurement principle only. The documentation for the specific differential pressure transmitters used is authoritative for installation, connection and calibration.

  • Monitor room pressure

    Compare two defined ranges. Small pressure increments, the reference point, and the permissible measurement deviation determine the selection. A changed measured value must be evaluated together with the operating condition.

  • Monitor filter pressure

    Compare the pressure before and after a filter. The operating range and evaluation follow this measurement task. The measured value does not replace a filter integrity test and is not direct evidence of the cleanroom class.

PREMASGARD for separate pressure measurement tasks

The PREMASGARD® 722x series has two measuring channels and switchable measuring ranges. It measures overpressure, underpressure, or differential pressure in suitable gaseous media. The series provides analog output signals of 0–10 V or 4–20 mA. The manufacturer's documentation lists cleanroom and filter technology among other applications.

For small room pressure levels, checking the product variant is particularly important: The product page of the linked PREMASGARD 7225 states an accuracy of ±13 Pa. At a pressure level of, for example, 15 Pa, this error margin may be too large. Choose this version only if its technical limitations are suitable for the respective measuring task. The product selection includes various versions and serves as a preliminary selection.

If temperature and humidity in the duct as well as a digital connection are also required, the PREMASGARD 8147-Modbus can perform another device function. Compare the arrangement of the measuring points before combining several measurements in one device.

View PREMASGARD 7225

Alerting and verification are part of planning

EU GMP Annex 1, Section 4.16, requires continuous monitoring and recording of pressure differentials classified as critical, as well as alerts for defined deviations. Any delays must be assessed and justified in the relevant contamination control strategy. These requirements apply to the overall system and cannot be met by a sensor alone.

For your project, the measurement point plan, calibration concept, signal testing and alarm response must be fully integrated. Please provide S+S with your pressure levels, accuracy requirements and interfaces for technical coordination.

Frequently Asked Questions about Differential Pressure in Cleanrooms

How much overpressure does a cleanroom need?

A universal overpressure value cannot be derived from the term cleanroom. Setpoints are determined by the protection concept, use, and applicable requirements. For sterile medicinal products, EU GMP Annex 1 provides a guideline for adjacent rooms of different grades. Do not apply this to other applications without verification; pressure levels and alarm limits are defined for the project.

What is a pressure cascade in a cleanroom?

A pressure cascade is a coordinated sequence of pressure levels between adjacent areas. In product protection, the more critical area is often at a higher pressure. The differences between the zones and the intended airflow are crucial. All figures must refer to traceable references so that setpoints and measurements can be compared.

Is a differential pressure switch sufficient for continuous pressure measurement?

A differential pressure switch provides a switching state when a threshold is reached. A pressure transmitter, on the other hand, provides a measured value or a corresponding output signal. If pressure trends are required, the measurement chain must be able to capture and record them. The required combination of measurement and switching function depends on the monitoring concept.

Why is the largest measuring range not always the best choice?

The permissible measurement deviation may depend on the upper end of the range. In such cases, a wide range for a small pressure step can lead to an unfavorable error assessment. Check the manufacturer's specifications at the intended operating point and take zero point and drift into account. Display resolution and maximum measuring range do not indicate the achievable accuracy by themselves.

Can filter differential pressure prove cleanroom quality?

Filter differential pressure describes the pressure loss across a filter under the respective operating conditions. It can provide information for the assessment of the equipment. It replaces neither a filter integrity test nor the measurements for cleanroom classification. Room pressure measurement also has a different purpose. Therefore, determine for each measuring point what information may be derived from it.