Cleanroom Monitoring: Sensors for Pressure, Temperature, and Humidity

Cleanroom monitoring records the environmental conditions relevant to a process and detects deviations. In terms of technical sensing, differential pressure, temperature, and relative humidity are the main focus. The key is the interplay of suitable measuring points, appropriate measuring devices, reliable data transmission, and a defined response. This guide is aimed at specialist planners, system manufacturers, and technical operators who want to structure measurement tasks in the cleanroom and its ventilation system.

Back to blog

What does cleanroom monitoring involve?

A cleanroom is operated for a specific purpose. Accordingly, the monitoring concept must define which conditions are relevant to the product, the process, and operations. A displayed temperature reading answers a different question than the pressure differential between the cleanroom and the airlock. Both values can be important for operations, but they are not interchangeable.

Temperature and humidity describe the indoor climate. Differential pressure helps assess the intended pressure conditions between areas. A pressure drop across an air filter, in turn, affects the condition of the air handling system. These tasks require measurement points with different reference parameters and measurement ranges.

Comprehensive cleanroom monitoring can also include particle measurement and, depending on the process, microbiological testing. The Pressure, temperature, and humidity sensors discussed here are part of this concept. A cleanroom class cannot be confirmed based on their measured values alone.

Therefore, start by specifying the measurement task and the measurement location. Then select the sensor, interface, and evaluation method. This ensures that it is clear which condition a measurement point is actually monitoring.

  • Ambient pressure

    Measure the pressure difference between defined areas. The reference chamber, sign, and operating condition are part of the measurement point description.

  • Temperature

    Measure the temperature at representative locations. Take local heat loads, doors, and air outlets into account when determining the positioning.

  • Relative Humidity

    Evaluate humidity in conjunction with temperature. Distinguish between the measurement range, permissible operating conditions, and cleaning processes.

  • Filter pressure

    Measure the pressure drop before and after a filter. This value describes a different phenomenon than the pressure cascade between rooms.

Measure indoor air and duct air at appropriate locations

A duct sensor measures the air at its installation location in the ventilation duct. This allows it, for example, to characterize the treated supply air. However, it does not prove that the same conditions prevail at every point in the cleanroom. Room measurements and duct measurements therefore each require a well-justified measurement location.

Factors affecting temperature and humidity include local heat sources, airflow, accessibility, and the intended cleaning procedures. The measurement point must accurately reflect the conditions being evaluated and must not be selected solely based on a convenient installation location. This also applies to the reference point for a room pressure measurement.

Our HYGRASGARD® KFF/KFTF products are used in cleanroom technology, among other applications. The specific model must be suitable for the medium, humidity conditions, and installation location. For example, a measurement range up to 100% relative humidity does not automatically mean that condensation is permissible during operation. Compare the variants in the Humidity Sensor Selection.

Integrating Sensors, Control, and Monitoring

Depending on the device, data transmission can be performed using standard analog signals such as 0–10 V or 4–20 mA, as well as digital interfaces. An analog signal must be scaled to the correct measurement range in the receiving system. For digital devices, the device address, register mapping, and communication settings, among other things, must be correct.

Modbus can transmit measured values to a building automation system or a higher-level system. However, the protocol alone does not handle either technical evaluation or alarm management. This article explains the basics What is Modbus?.

For each measured variable, you must specify how it is to be displayed, stored, and evaluated. Also, verify the system’s behavior in the event of a missing or implausible value. Whether control and monitoring require separate measurement chains depends on the respective risk and monitoring strategy.

Be sure to include calibration and functional tests in your planning. This involves examining the entire measurement chain: sensor, transmission, scaling, display, and, if applicable, recording. A correct sensor reading is of little use if the receiving system uses a different unit or scaling.

  • Combining Metrics

    A combination sensor can measure multiple parameters at a suitable installation location. Verify that this location is representative of all parameters and that the measurement range, accuracy, and signal path are appropriate in each case.

  • Divide Measurement Points

    Separate devices are useful when measurement locations, reference points, or requirements differ. For example, a temperature measurement in the room and a filter pressure measurement in the ventilation system are taken at different locations.

Select S+S Sensors for Your Measurement Application

The PREMASGARD® 8147-Modbus combines the measurement of temperature and relative humidity in the duct with a Pressure or differential pressure measurement. The device transmits measured values via Modbus. Its applications include cleanroom, medical, and filtration technology, among others.

This combination may be suitable for the intended measurement task if the duct installation location, pressure tapping points, and technical requirements are compatible. Suitability for a specific room pressure level must be verified based on the permissible measurement error at the operating point; the wide pressure measurement range alone is not sufficient proof of this.

The humidity sensor selection above shows the general product range; it is not a blanket-approved cleanroom bill of materials. For separate pressure measurement tasks, you will find additional Pressure Transducer. To make your selection, specify the measurement location, operating range, required accuracy, and interface.

View PREMASGARD 8147-Modbus

From the Application Scenario to the Right Measurement Chain

A sound concept combines the measurement task with a suitable installation location and a clear operational response. Use the product selection to narrow down your options based on technical criteria, and determine the specific design based on your project requirements. Via Help and Contact You can discuss your measurement task with an expert from the S+S Regeltechnik team.

Frequently Asked Questions About Cleanroom Monitoring

What sensors are needed for cleanroom monitoring?

The selection depends on the process and the monitoring concept. For technical environmental conditions, differential pressure, temperature, and humidity sensors are particularly suitable. Filter pressure and other parameters may also be included. Comprehensive cleanroom monitoring may also require particle measurement and microbiological testing. Therefore, the selection process begins with the measurement tasks rather than with a generic list of devices.

Can a sensor in the ventilation duct replace room monitoring?

A duct sensor measures the air at its specific installation location. This does not provide evidence of conditions at all locations in the room. Whether duct measurements are sufficient for a specific application or whether additional in-room measurement points are required must be determined based on airflow patterns, the process, and qualification. The measurement location and the meaning of the value are clearly linked.

Do fixed temperature and humidity limits make sense for all cleanrooms?

Temperature and humidity limits must be appropriate for the process and the specific operating requirements. No universal target value can be derived from the term “cleanroom.” Define the operating range, permissible deviations, and alarm thresholds for the specific application, and then determine which devices meet these requirements at the intended measurement location.

Does Modbus already provide a complete monitoring system?

Modbus transmits data between devices and higher-level systems. Data logging, alarms, user permissions, and operational responses must be configured within the overall system. During commissioning, register mapping, units, scaling, and failure behavior must be verified. Therefore, the presence of a Modbus interface does not automatically confirm that the entire system is suitable for a regulated application.

Are all humidity sensors suitable for cleaning and condensation?

Suitability depends on the specific application. Consider the measurement range, permissible environmental conditions, and resistance to cleaning agents. Even a high enclosure protection rating is not a universal guarantee of the measuring element’s resistance. Review the instrument documentation, installation conditions, and the intended cleaning process together before selecting a model for the cleanroom.